2351TEM_DBL_LST_EN_0850.PDF • PAGE 1
ABuilding Safety. Building Security.
Optical-Thermal Detector
2351TEM
Description
The Optical-Thermal Detector 2351TEM uses both the
scattered light principle as well as a separate thermal
detection unit. It was developed to detect the charac-
teristics of re in a wide range of applications, and to
avoid deceptive alarms. The modern design of both
measurement systems and the analysis of the parame-
ters by means of a special algorithm allow to reliably
evaluate the characteristics of re. This makes it an
all-rounder that is used in virtually all elds of re de-
tection.
An internal drift compensation adjusts the alarm thres-
hold by continually evaluating the contamination of the
detector. With that, the sensitivity of the detector is
kept constant for a long time.
The thermal sensor complies with Class A1R accor-
ding to EN 54-5. The detector can therefore be used in
rooms with a maximum height of 7.5m.
Addressable conventional technology is used for alarm
transmission to the re detection control panel. The
detector addressing can be achieved in 2 ways:
A detector with an Address Module NG58-1 can be
individually identifi ed by the suitable control panel.
An address, which has been stored in the detector
by means of the Remote Programming and Test Unit,
is displayed on the Zonal Display Unit S300ZDU.
A test activation of the detector can be carried out
using the Remote Test Unit ECO1000RTU. In addition
to the test activation of the detector, the Remote Pro-
gramming and Test Unit S300RPTU can also be used
to set and display the following detector parameters:
the sensitivity in 3 levels,
the detector address, and
the date of the previous maintenance.
Furthermore, the degree of drift compensation (de-
tector contamination) and the current condition of the
detector can be read out.
The detector can be attached to various detector ba-
ses and it can be protected against theft.
Addressable conventional technology
Combination of optical and thermal
characteristics of fi re
Drift compensation
Sensitivity selectable in 3 steps
Addressing by means of address
module or detector parameterisation
Function testable with Remote Test
Unit ECO1000RTU