ABuilding Safety. Building Security.
Thermal ROR Detector
ECO1005
Description
The Thermal ROR Detector ECO1005 reacts to tem-
perature changes within defi ned periods of time, up
to a maximum temperature of 58°C. The intelligent
evaluation of these data allows the early detection of
spreading fi res.
Addressable conventional technology is used for alarm
transmission to the re detection control panel. By
means of the Address Module NG58-1, each detector
can be addressed individually.
A test activation of the detector can be carried out
using the Remote Test Unit ECO1000RTU. The detec-
tor can be attached to various detector bases and it
can be protected against theft.
Addressable conventional technology
Maximum temperature 58°C
Individual detector addressing by
means of optional address module
Optional connection of remote
indicator
Function testable with Remote Test
Unit ECO1000RTU
Specifi cations
Operating voltage Supply through the detector line voltage
Current consumption typ. 75µA (quiescent)
Alarm temperature 58°C (maximum-heat component)
Operating temperature max. +45°C
Ambient temperature -30°C to +70°C
Relative humidity 5 – 95% (no condensation)
Dimensions ø × H 102 × 40.5 (mm)
Colour white
Weight 70g
Approval VdS G201016
Order number 242045
Order name Thermal ROR Detector/Conv./1000/SS ECO1005